P.090 diagnostics source, P.091 diagnostics display – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 139

Advertising
background image

Programming Reference

4-53

The status of the digital inputs (selected by entering a value of 1, 2, or 4 in P.090) is

P.090 Diagnostics Source

This parameter is

used to select

internal information

such as I/O data,

network statistics,

etc., for display in

parameter P.091.

Parameter Range:

0 = Diagnostic not used
1 = Terminal strip digital inputs 4, 3, 2, 1
2 = Terminal strip digital inputs 8, 7, 6, 5
3 = Terminal strip analog input normalized to speed

(see Appendix G)

4 = RMI digital inputs 4, 3, 2, 1
5 = RMI analog input (see Appendix G)
6 = RMI frequency input (see Appendix G)
7 = Encoder data
8 = DC bus voltage

9 = Terminal strip analog input scaled (see

Appendix G)

10 = Terminal strip analog input with P.009 (Terminal

Strip Analog Input Offset) applied (see

Appendix G)

11 = Analog input stop threshold (see Appendix G)
12 = Analog input start threshold (see Appendix G)
14 = Network interface: number of messages

received from the network

15 = Network interface: number of message receive

time-out errors

16 = Network interface: number of message CRC

errors

17 = Network interface: number of message overrun

errors

18 = Network interface: number of messages

aborted

19 = Network interface: number of messages

transmitted to the network

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.091 Diagnostics Display

P.091 Diagnostics Display

This parameter

displays the data

selected in P090.

Parameter Range:

N/A

Default Setting:

N/A

Parameter Type:

N/A

Refer also to parameters:

P.090 Diagnostics Source