Programming Reference

4-57

H.003 Torque Boost Voltage

(continued)

The level of increased output frequency is a function of the value entered in H.004 and

the motor current.

Actual motor shaft speed is determined by two factors: inverter output frequency and

the slip of the motor. The speed reference is converted into output frequency. Motor

slip varies with load and is determined by the type of induction motor.

At rated load, slip compensation measures inverter output current and increases the

output frequency by the percentage entered in H.004. Below rated load, slip

compensation will increase inverter output frequency by the percentage in H.004

multiplied by the percent of rated load.

Because of load changes, the long-term speed behavior of the motor is greatly

improved through the use of this parameter.

To calculate the value entered for H.004, use the following equation:

H.004 = 100 x Synchronous RPM - Nameplate RPM x Max Power Module Amps

Synchronous RPM Motor Nominal Current

Figure 4.11 – Torque Boost Voltage



Base Frequency

Voltage

Output

%

Output Frequency

(Hz)





Constant

V/Hz

Ratio

Torque Boost
H.003 = 1%

H.004 Slip Compensation

This parameter is

used to improve

motor speed

regulation by

increasing the output

frequency applied to

the motor (the

percentage of

frequency rise at

Power Module Output

Amps (P.095)).

Parameter Range:

0.0% to 10.0% of base frequency (H.001)

Default Setting:

0.0% (no slip compensation)

Parameter Type:

Tunable

Refer also to parameters:

P.095 Power Module Output Amps

H.001 Motor Nameplate Base Frequency