4-30

GV3000/SE AC Drive Software Reference, Version 6.06

P.025 Stop Type

(continued)

If RUN is selected:

If P.025 = 0, pressing the STOP/RESET key or giving an external stop command will

cause the motor to coast to rest.

If P.025 = 1, pressing the STOP/RESET key or giving an external stop command will

cause the motor to ramp to rest within a time equal to or greater than the preset

deceleration time (P.002/P.018).

If JOG is selected:

When the START input from the selected control source is released (unasserted), the

motor will ramp down in speed regardless of the value in P.025.

Pressing the STOP/RESET key or giving an external stop command when JOG is

selected will stop the motor differently depending on whether the drive is configured

for V/Hz or vector regulation:

For V/Hz regulation, the motor will always perform a ramp stop regardless of the value

in P.025.

For vector regulation, the motor will stop based on the value of P.025:

If P.025 = 0, pressing the STOP/RESET key or giving an external stop command will
cause the motor to coast to rest.

If P.025 = 1, pressing the STOP/RESET key or giving an external stop command will
cause the motor to ramp to rest within a time equal to or greater than the preset

deceleration time (P.022).

If a function loss occurs, the motor will coast to rest. If P.026 = 0, a function loss fault

will be generated, and FL will be displayed.

P.026 Function Loss Response

This parameter

specifies how the

drive will respond to

an open circuit

between terminal

strip inputs 16 and

20.

Parameter Range:

0 = Generate a fault (IET) and coast to rest

1 = Coast to rest without a fault

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.013 Output Relay Configuration