Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 181

Advertising
background image

Troubleshooting the Drive Using Error Codes

5-5

OCb

Overcurrent

(at DC braking)

DC voltage too high.

Check parameters H.006, H.007.

OCd

Overcurrent (at

deceleration)

Overcurrent condition occurred while

decelerating. Deceleration time too

short.

See OC fault corrective actions.

Increase deceleration time (P.002,

P.018, P.022)

OF

Overfrequency

Drive has exceeded maximum

allowable output frequency.

Regenerating energy is too high.

Stability or slip compensation circuit

adds frequency reference.

If H.016 ON, searching current is too

high. Motor is too small.

Vector: Check parameters Encoder

PPR (U.001), Motor Poles (U.002),

Base Frequency (U.003).
V/Hz: Check DC bus voltage; increase

decelerating time. Check values

Maximum Speed (P.004) / Overfreq.

(H.022). Check slip compensation

(H.004).

If H.016 ON, check motor size versus

Power Module size, recheck setting of

P.005 (too high).

OH

Drive

overtemperature

Cooling fan failure.

Check ambient temperature, cooling

fan, minimum clearances around drive.

OL

Motor overload

Excess motor current.

V/Hz: Torque boost too high, therm.

overload level too low.

Vector: Check actual/Motor Rated

Nameplate Amps (U.004)

V/Hz: Check actual current/Torque

Boost (H.003).

Check that Power Module is sized

correctly.

Reduce load on motor (for example, at

low frequency).

Excess load on motor, for example, at

too low speeds.

Check that Power Module is sized

correctly. Reduce load on motor (e.g.,

at low frequency).

Loss of phase connection.

Check output lines to the motor.

OPL

Motor output phase

loss

Phase lost between drive and motor.

Check connections and cable of all 3

phases and motor windings. Replace

any damaged cable.

OSP

Overspeed

(Vector only)

RPM above 130% Maximum Speed

(P.004), speed regulator

response not optimized.

Check Encoder PPR (U.001), Motor

Poles (U.002), Base Frequency

(U.003), Motor Nameplate RPM

Speed (U.005). Check Reg.

Proportional (U.012) Integral Gain

(U.013)

PUc

Missing Power

Module ID

connector

Bad or disconnected cable between

Regulator and Power Module.

Check cables between Regulator

board and Power Module.

PUn

Power Module not

identified

Drive parameters have been restored

to power-up defaults. Regulator has

not been configured to match Power

Module.

Power Module must be configured by

Reliance service personnel.

PUo

Drive power

electronic

overload

Power Module overloaded.

Too high DC Braking Current

(H.007) or Torque Boost (H.003).

Check load to Power Module.

Check Power Module sizing versus

application. Check DC Braking Current

value (H.007). Check Torque Boost

(H.003).

Table 5.2 – List of Fault Codes (Continued)

Code

Fault

Description

Fault Cause

Corrective Action