U.005 motor nameplate rpm – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 158

Advertising
background image

4-72

GV3000/SE AC Drive Software Reference, Version 6.06

*The actual adjustment range changes based on the values in U.002 (Motor Poles)

and U.003 (Motor Nameplate Base Frequency):

In general, the value range for U.005 is:

U.003 x 120 x .900 to U.003 x 120 x .999

U.002 U.002

If the value is too close to the synchronous RPM, the drive may exhibit instability. This

value directly affects torque linearity and the maximum attainable horsepower.

If you change this parameter after performing self-tuning using parameter U.008, you

must repeat the self-tuning procedure.

U.005 Motor Nameplate RPM

This parameter

identifies the motor

rated RPM as it

appears on the motor

nameplate.

This parameter must

be set prior to

activating the torque

control self-tuning

procedure (U.008).

Parameter Range:

*

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters:

U.002 Motor Poles

U.003 Motor Nameplate Base Frequency

U.008 Torque Self-Tune Enable

Motor Poles

(U.002)

Base Frequency

60 Hz (U.003)

Base Frequency

50 Hz (U.003)

2

4

6

8

3240-3596

1620-1798

1080-1198

810-899

2700-2997

1350-1498

900-999

675-749

!

ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002

(Motor Poles), U.003 (Motor Nameplate Base Frequency), U.005 (Motor

Nameplate RPM), and U.017 (Motor Top Speed) determines the motor

maximum speed. These parameters must be set by a qualified person

who understands the significance of setting them accurately. Failure to

observe this precaution could result in bodily injury.