The keypad, 5 the keypad – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 82

Advertising
background image

3-6

GV3000/SE AC Drive Software Reference, Version 6.06

3.5 The Keypad

The drive’s keypad has nine membrane keys that are used to monitor, program, and
control the drive.

If the control source is changed, the AUTO/MAN selection may be

changed as well. When the control source is changed to OP or rE,

the AUTO/MAN selection is forced to AUTO. If the control source is

changed to LOCL or SErL, the AUTO/MAN selection is forced to

MANUAL. However, if the control source is changed from LOCL or

SErL or vice versa, the AUTO/MAN selection is not changed.

Note that this key is not active if the control source is SErL. Refer to

the P.000 parameter description for more information on control

source selection.

Refer to the following parameters for more information on the

AUTO/MAN key:

P.052 AUTO/MAN Key Disable

P.053 Manual Reference Preset Enable

Use the AUTO/MAN key to switch between the auto speed reference

and the manual speed reference as shown below.

AUTO/MAN

Status

Control Source (P.000)

Speed Reference

Source

AUTO selected Local keypad/display

(P.000=LOCL)

Terminal strip

Terminal strip remote

inputs (P.000=rE)

Terminal strip

Option port (P.000=OP)

Network

Serial port (P.000=SErL)

Terminal strip

MAN selected Local keypad/display

(P.000=LOCL)

Local keypad/display

or OIM/CS3000

Terminal strip remote

inputs (P.000=rE)

Local keypad/display

or OIM/CS3000

Option port (P.000=OP)

Local keypad/display

or OIM/CS3000

Serial port (P.000=SErL)

Local keypad/display

or OIM/CS3000

!

ATTENTION: When switching from auto to manual, or

manual to auto, the drive will ramp to the reference level

provided by the new source at the rate specified in P.001

(Accel Time 1), P.002 (Decel Time 1), P.017 (Accel Time

2), or P.018 (Decel Time 2). Be aware that an abrupt

speed change may occur depending upon the new

reference level and the rate specified in these

parameters. Failure to observe this precaution could

result in bodily injury.

AUTO

MAN

Advertising