H.005 dc braking enable – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 144

Advertising
background image

4-58

GV3000/SE AC Drive Software Reference, Version 6.06

H.004 Slip Compensation

(continued)

Synchronous RPM = 120 x F

No. of Motor Poles

Example: 1722 RPM

Motor Nominal Current = 78% of Maximum Power Module Amps (P.095)

V/Hz regulation

2 kHz

H.004 = 100 x 1800 - 1722 x 100% = 5.56%

1800 78%

If the parameter is set to zero, motor speed will not be proportional to reference, but

will vary depending on load.

Important: This function will not provide holding torque as a mechanical brake. DC

braking is only operative when Stop Type (P.025) is set to 1 (ramp stop).

DC braking is used to provide additional motor braking (by DC current flow through

motor windings) at speeds below DC Braking Start Frequency (H.006). If DC braking

is required, DC braking functions (H.008, H.007) must be greater than zero (0).

When the motor decelerates to the preset DC Braking Start Frequency (H.006), the

DC Braking Current (H.007) is applied to the motor after a Power Module-dependent

delay time.

H.005 DC Braking Enable

This parameter

enables or disables

DC braking.

Parameter Range:

ON = Enable DC braking
OFF = Disable DC braking

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.025 Stop Type

H.006 DC Braking Start Frequency

H.007 DC Braking Current

H.008 DC Braking Time

H.017 Input Power/Snubber Configuration