Programming Reference

4-63

.

For AC input Power Modules (200-230 V, 3-phase, 50/60 Hz or 380-460 V, 3-phase,

50/60 Hz), set H.017 = 0 or 1.

For DC input Power Modules, set H.017 = 2 or 3 if multiple motors are connected to

the inverter. Set H.017 = 4 or 5 if a single motor is connected to the inverter.

Snubber Resistor

If a snubber resistor is not used, set H.017 = 0, 2, or 4. If the DC bus voltage rises

above a certain threshold (14% above the rectified nominal AC line), the drive will

increase the commanded frequency in an effort to reduce bus voltage. The drive will

increase the commanded frequency a maximum of 10 Hz but will not exceed the value

specified in P.004 (Maximum Speed). The deceleration time (P.002) may be

automatically extended to prevent a high bus voltage fault from occurring. If the bus

voltage continues to rise, a high bus voltage fault (HU) will be generated.

If a snubber resistor is used, set H.017 = 1, 3, or 5. If the DC bus voltage rises above a

certain threshold (14% above the rectified nominal AC line), the drive will not attempt

to increase the commanded frequency, but will rely on the hardware snubber resistor

to decrease voltage. Note that you may need to extend the deceleration time specified

in P.002 (Decel Time) to prevent a high bus voltage fault (HU) from occurring.

H.017 Input Power/Snubber Configuration

This parameter is

used to identify the

input power supply

type/snubber

resistor/line dip

ride-through

configuration being

used.

Parameter Range:

0 = AC input, snubber resistor not used,

ride-through enabled

1 = AC input, snubber resistor used,

ride-through enabled

2 = DC input, snubber resistor not used,

ride-through disabled

3 = DC input, snubber resistor used,

ride-through disabled

4 = DC input, snubber resistor not used;

ride-through enabled

5 = DC input, snubber resistor used,

ride-through enabled

Default Setting:

0

*

Parameter Type:

Configurable

Refer also to parameters:

P.042 Line Dip Ride-Through Time

P.002 Decel Time 1

*

For M/N 50R416x, 50T416x, 75R416x, 75T416x, and 125R416x (DC input), the default value = 4.

!

ATTENTION: When connected to a non-regenerative common DC bus,

regeneration may cause a rise in DC bus voltage. Be aware that other

drives on the bus may experience an unexpected speed increase due to

the high bus voltage. Failure to observe this precaution may result in

bodily injury.