H.002 motor nameplate amps, H.003 torque boost voltage – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 142

Advertising
background image

4-56

GV3000/SE AC Drive Software Reference, Version 6.06

Important: If you set H.003 = 0, you must perform the identification test (using H.020)

prior to running.

Torque boost is required to offset the voltage drop of the AC motor at low speeds. For

high friction loads and high inertia loads, high starting torque may be needed.

Increasing Torque Boost Voltage will increase motor starting torque. See figure 4.11.

If the torque boost voltage setting (H.003) is too high, the motor may draw excessive

starting current, resulting in an OL or PUo fault, or the drive may go into current limit

and not accelerate. When H.003 = 0, the drive automatically provides torque boost

voltage that is a function of motor load. If the motor does not accelerate or a fault

occurs, set parameter H.003 equal to 0.

H.002 Motor Nameplate Amps

This parameter is the

motor amp rating as it

appears on the motor

nameplate.

Parameter Range:

Power Module-dependent

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters:

P.005 Current Limit

!

ATTENTION: This parameter must not exceed the rated amps found on

the motor nameplate. Excess heating of the motor could result if this is

not done. Failure to observe this precaution could result in damage to,

or destruction of, the equipment.

H.003 Torque Boost Voltage

This parameter sets

the percentage of

output voltage boost

at zero frequency. It

is set as a

percentage of Motor

Nameplate Volts

(H.000).

Parameter Range:

0.0% to 20.0% of nominal inverter voltage

Default Setting:

0.5%

Parameter Type:

Configurable

Refer also to parameters:

H.000 Motor Nameplate Volts

Advertising