Programming Reference

4-19

For more information about the analog input, refer to Appendix G.

Important: Verify that the hardware (jumper J4) and software configurations match

each other and the external signal.

P.010 Terminal Strip Analog Input Gain

This parameter is

used to compensate

for component

tolerance errors or

insufficient voltage

from the input

reference source at

the terminal strip.

This parameter is not

used if the terminal

strip analog input is

used as vector torque

reference

(U.000 = 1).

Parameter Range:

0.100 to 5.000

Default Setting:

1.000

Parameter Type:

Tunable

Refer also to parameters:

P.000 Control Source

P.011 Terminal Strip Analog Input Configure

This parameter

selects the type of

analog input signal

being used and

whether to invert it

(negate it) after it has

been converted from

analog to digital by

the drive.

If the terminal strip

analog input is used

as vector torque

reference

(U.000 = 1), this

parameter is used

only to enable the

analog input signal

loss detection

feature.

Parameter Range:

Jumper J4 on pins

2 and 3

Jumper J4 on pins

1 and 2

Jumper J4 on pins

2 and 3

0 = +/- 10 VDC
1 = +/- 10 VDC inverted
2 = 0 to 10 VDC
3 = 0 to 10 VDC inverted
4 = 4 to 20 mA. Generate fault on signal loss.
5 = 4 to 20 mA inverted. Generate fault on signal

loss.

6 = 0 to 20 mA
7 = 0 to 20 mA inverted
8 = 4 to 20 mA. Display alarm and use previous

reference on signal loss.

9 = 4 to 20 mA inverted. Display alarm and use

previous reference on signal loss.

10= 4 to 20 mA. Display alarm and use Preset

Speed 1 (P.031) as reference on signal loss.

11= 4 to 20 mA inverted. Display alarm and use

Preset Speed 1 (P.031) as reference on signal

loss.

12= 0 to 10 VDC.

Start and stop the drive based on

analog input value. (P.000 must be set to rE.)

See section G.4 if you select this option.

Default Setting:

2

Parameter Type:

Configurable

Refer also to parameters:

P.009 Terminal Strip Analog Input Offset

P.010 Terminal Strip Analog Input Gain