Programming Reference

4-25

In V/Hz regulation, this parameter specifies the time in which the motor ramps from

zero speed to Maximum Speed (P.004).

In vector regulation, this parameter specifies the time in which the motor ramps from

zero speed to Motor Top Speed (U.017).

The time it takes the motor to make any speed increase is directly proportional to the

value in this parameter. This parameter does not apply if JOG is selected.

In V/Hz regulation, this parameter specifies the time in which motor speed ramps from

Maximum Speed (P.004) to zero speed.

In vector regulation, this parameter specifies the time in which motor speed ramps

from Motor Top Speed (U.017) to zero speed.

The time it takes the motor to make any speed decrease (except a coast-to-rest stop)

is directly proportional to the value in this parameter.

This parameter does not apply if JOG is selected.

P.017 Accel Time 2 (RAMP 2)

This parameter sets

the acceleration time

when a second ramp

selection is

configured as a

digital input.

When the RAMP 2

acceleration time

digital input is

asserted, the

RAMP 2 deceleration

time also takes effect.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)

0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters:

P.001 Accel Time 1

P.007 Terminal Strip Digital Inputs Configure

P.018 Decel Time 2 (RAMP 2)

This parameter

specifies the

deceleration time

when a second ramp

selection is

configured as a

digital input.

When the RAMP 2

deceleration time

digital input is

asserted, the RAMP

2 acceleration time

also takes effect.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)

0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters:

P.002 Decel Time 1

P.007 Terminal Strip Digital Inputs Configure