4-16

GV3000/SE AC Drive Software Reference, Version 6.06

P.007 Terminal Strip Digital Inputs Configure

(continued)

TRQ/SPD

TRQ/SPD allows you to switch between torque regulation and speed regulation while

the drive is running or stopped. This feature only applies when the drive has been

configured as a vector regulator (P.048 = UEC), and U.000 (Torque Reference

Source) > 0.

To provide smooth transitioning when switching from torque to speed, the speed

regulator is preset with the last torque reference. When switching from speed to

torque, the torque regulator will switch to the new torque reference.

The digital input for TRQ/SPD is active if the control source is local, remote, or serial.

Interaction with P.008

The default value of 0 for P.007 will limit P.008 (Terminal Strip Speed Reference

Source) to a selection of 0. You must change P.007 to some value other than 0 in order

to change P.008 to some value other than 0. See table 4.3 and the selection example

in the P.008 parameter description.

Refer to the GV3000/SE hardware reference manual for terminal strip wiring.