H.021 ac line volts, H.022 overfrequency limit – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 153

Advertising
background image

Programming Reference

4-67

H.020 Identification Request

(continued)

Do not connect a motor that cannot withstand maximum Power Module Output Amps

reduced by selected Current Limit (P.005).

Note that the identification procedure must not be performed when more than one

motor is being driven by the inverter.

To activate the identification procedure after it has been enabled (H.020 = ON), the

program mode must be exited. I-En will flash on the display to indicate the procedure

has been enabled. The keypad START key must be pressed to start the procedure.

I-Ac will flash on the display to indicate the procedure is being performed (active). The

results of this procedure are written to parameter H.019.

If the fault code nId is displayed after a start command is asserted, it indicates that the

identification procedure has not been performed. Reset the fault, and then perform the

procedure.

If a fault or a stop command is detected, the procedure will abort. HId will be displayed

if the procedure is aborted. Refer to Identification Result (H.019).

The value entered should be within 10% of actual line voltage. If this parameter is set

too low, it may cause a drive fault on overvoltage.

If actual frequency exceeds the set value, the inverter will fault (OF will be displayed

on the keypad/display) and the drive will stop.

The overfrequency limit should be set approximately 15 Hz above Maximum Speed

(P.004).

H.021 AC Line Volts

This parameter is the

phase-to-phase line

voltage provided to

the drive input power

terminals.

Parameter Range:

300 to 565 VAC

Default Setting:

460

Parameter Type:

Configurable

Refer also to parameters:

N/A

H.022 Overfrequency Limit

This parameter

provides overspeed

protection by setting

the fault level for

maximum frequency

output.

Parameter Range:

30.0 to 4 x H.001 + 5% or 210 Hz

*

Default Setting:

90.0

Parameter Type:

Configurable

Refer also to parameters:

P.004 Maximum Speed

*

Drive will use the lesser value.

!

ATTENTION: The user is responsible for ensuring that driven machinery,

all drive-train mechanisms, and application material are capable of safe

operation at the overfrequency limit. Failure to observe this precaution

could result in bodily injury.

Advertising