Programming Reference

4-23

Selections 5 through 9 are available only if an optional RMI board is installed in the

drive. Refer to instruction manual D2-3341 for more information about the RMI board.

P.014 Trim Reference Source

This parameter

specifies the source

for the trim reference.

Trim reference is

added to the speed

reference.

Refer to figure 4.3.

Parameter Range:

0 = No trim reference used
1 = Terminal strip analog input
2 = Option port trim reference register
3 = Maximum speed
4 = Torque current feedback (vector only)
5 = RMI board analog input
6 = RMI board frequency input
7 = Switched RMI board analog input or frequency

input

8 = RMI outer loop PI block (Mode 1)
9 = RMI outer loop PI block (Mode 2)

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

P.015 Trim Gain Percentage

Figure 4.3 – Trim Reference Source Selection