U.031 svc sync direction, U.032 svc flux current regulator gain – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 171

Advertising
background image

Programming Reference

4-85

Note that when Forward/Reverse Configuration (P.027) is set to 1, setting this
parameter to r, Fr, or rF may still cause the motor to operate in the reverse direction.

On lower horsepower motors, the value can be increased to allow faster acceleration

and deceleration.

U.031 SVC Sync Direction

When starting into a

rotating load is

required, this

parameter selects the

direction in which the

drive will search in

order to synchronize

to motor speed.

Parameter Range:

OFF = Disable synchronization
F = Search starts in motor forward direction
r = Search starts in motor reverse direction
Fr = Search starts in motor forward then reverse

direction

rF = Search starts in motor reverse then forward

direction

Default Setting:

OFF

Parameter Type:

Configurable

Refer also to parameters:

N/A

!

ATTENTION: When starting with search enabled, there will be a several

second delay, and the motor may drift in the forward and reverse direction,

before the motor begins operating in the desired direction even if reverse

has been disabled in P.027. Stay clear of rotating machinery. Failure to

observe this precaution could result in bodily injury.

U.032 SVC Flux Current Regulator Gain

This parameter

specifies the gain of

the flux current

regulator.

For most

applications, it is

recommended that

this parameter not be

adjusted.

This parameter

applies to SVC

operation only.

Parameter Range:

100 to 1500 radians/sec

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Tunable

Refer also to parameters:

U.012 Speed Regulator Proportional Gain

U.013 Speed Regulator Integral Gain

U.030 SVC Slip Adjust