GV3000/SE AC Drive Software Reference, Version 6.06

To prevent unauthorized password use, a zero value (not the saved password value) is

displayed whenever this parameter is accessed.

Note that parameter values and the local keypad status are retained through a line dip

or power shutdown.

4.5 First Menu Parameters

The First Menu contains General parameters that are most commonly used for simple

applications. No password is required to access them. These parameters apply to

both vector and V/Hz programming and are described in detail in section 4.5.1.

4.5.1 First Menu General Parameter Descriptions (P.000 to P.006)

The selected drive control source is determined primarily by the value in P.000.

However, if P.000 = rE, then the REM/LOC input may toggle the control source

between the local keypad and the terminal strip. See P.007 (Terminal Strip Digital

Inputs Configure).

Depending on the control source selected, the AUTO/MAN key can be used to switch

between speed reference sources as shown in table 4.1.

P.000 Control Source

This parameter

selects the drive

control source.

The drive responds to

the reference,

forward/reverse,

run/jog, and start

commands (inputs)

only from the source

selected in this

parameter.

Parameter Range:

LOCL = Local keypad/display

rE = Terminal strip remote inputs
OP = Option port

*

SErL = Serial port (CS3000 or OIM

**

)

*

OP selection is not available if a network option board is not installed.

**

For more information about the Control and Configuration Software (CS3000), refer to instruction manual

D2-3348. For more information about the GV3000/SE OIM (Operator Interface Module, M/N 2RK3000),
refer to instruction manual D2-3342.

Default Setting:

LOCL

Parameter Type:

Configurable

Refer also to parameters:

P.007 Terminal Strip Digital Inputs Configure

P.008 Terminal Strip Speed Reference Source

P.063 Option Port: Network Reference Source

!

ATTENTION: In V/Hz regulation, if P.000 (Control Source) is set to OP

(Option Port), and P.062 is set to 1 (Hold Last Reference), and the drive

loses communication with the network, the drive will maintain the last

frequency command sent to it. Ensure that driven machinery, all

drive-train mechanisms, and application material are capable of safe

operation at the maximum operating speed of the drive. Failure to

observe this precaution could result in bodily injury.