P.013 output relay configuration – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 108

Advertising
background image

4-22

GV3000/SE AC Drive Software Reference, Version 6.06

For example, for an application using an output contactor, you can obtain a 0.5 second

delay between a start assertion and the generation of motor voltage by setting P.013

to 1. The delay will provide time for the contactor to close before motor voltage is

generated.

P.013 Output Relay Configuration

This parameter

specifies the type of

status indication

provided by the

output relay contacts

(terminals 28, 29, 30,

and 31 on the drive’s

terminal strip).

Parameter Range:

0 = Output relay is energized when one or more

faults (IET) are active.

1 = Output relay is energized to show state of drive

running with 0.5 second delay added between a

start assertion and generation of motor voltage.

2 = Output relay is energized to show state of drive

running but without 0.5 second start delay.

3 = Output relay is energized when network

communication is active.

4 = Output relay is energized when all start

permissive conditions are met.

5 = Output relay is energized when one or more

alarms are active.

6 = Output relay is energized when no faults are

active.

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

N/A