4-7

P.000 Control Source

(continued)

Refer to chapter 3 and the description of parameter P.052 (AUTO/MAN Key Disable) in

chapter 4 for more information on the AUTO/MAN key.

Set P.000 = OP to select the DeviceNet

 Network option board, the AutoMax

Network option board, the

PROFIBUS

 Interface board, or the ControlNet Network

option board as the drive control source.

Note that the REMOTE LED will turn on if any control source other than the local
keypad is selected.

The time the motor takes to make any speed increase is directly proportional to the

value in this parameter. This parameter does not apply if JOG is selected. See P.021

(Jog Ramp Accel Time).

If the motor load inertia is high, or the Current Limit (P.005) setting is too low, actual

motor acceleration time will be longer than the time set in P.001. If Accel Time 1 is set

too short, an overcurrent fault may occur.

Table 4.1 – Speed Reference Source Based on P.000 and AUTO/MAN Key Status

Control Source (P.000)

AUTO/MAN Status

Speed Reference Source

Local keypad/display

(P.000=LOCL)

AUTO selected

Terminal strip

MAN selected

Local keypad/display or OIM

Terminal strip remote

inputs (P.000=rE)

AUTO selected

Terminal strip

MAN selected

Local keypad/display or OIM

Option port (P.000=OP)

AUTO selected

Network

MAN selected

Local keypad/display or OIM

Serial port (P.000=SErL)

AUTO selected

Terminal strip

MAN selected

Local keypad/display or OIM

P.001 Accel Time 1 (RAMP 1)

For V/Hz regulation,

this parameter

specifies the amount

of time in which the

motor ramps from

zero speed to

Maximum Speed

(P.004).

For vector regulation,

this parameter

specifies the amount

of time in which the

motor ramps from

zero speed to Motor

Top Speed (U.017).

Parameter Range:

1.0 to 999.9 seconds (V/Hz)

0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters:

P.004 Maximum Speed

P.005 Current Limit

U.017 Motor Top Speed