U.021 rotor time constant / fast flux up – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 166

Advertising
background image

4-80

GV3000/SE AC Drive Software Reference, Version 6.06

For special motors or for motors with base speeds < 1150 RPM, the rotor time

constant must be calculated by evaluating equivalent motor circuit data as shown in

figure 4.14.

To calculate the rotor time constant, use the following formula:

Rotor time constant = L / R2

Where:

L = Lm + L2

Lm = Xm / 2 x 3.14 x 60

L2 = X2 / 2 x 3.14 x 60

Fast Flux-Up Feature (SVC Only)

The fast flux-up feature, available for drives configured for SVC operation only,

significantly reduces the delay between the initiation of a run command and the actual

motor shaft turning.

Setting U.021 to 0 enables the fast flux-up feature. Parameter U.031 (SVC Sync

Direction) must be set to OFF to use this feature.

Note that this parameter is not functional in versions 6.0 through 6.05.

U.021 Rotor Time Constant / Fast Flux Up

This parameter

determines the

performance of the

magnetizing current

regulator.

For most

applications, it is

recommended that

this parameter not be

changed.

For SVC operation,

this parameter is

used to enable the

fast flux-up feature.

Parameter Range:

0 to 9999 ms

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Tunable

Refer also to parameters:

N/A

Figure 4.14 – Motor Equivalent Circuit Diagram for Calculating Rotor Time Constant