P.048 volts/hertz or vector regulation, P.049 country defaults – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 126

Advertising
background image

4-40

GV3000/SE AC Drive Software Reference, Version 6.06

For V/Hz control, the drive provides open-loop volts per hertz regulation which is

appropriate for general purpose applications.

For vector control, you may select either flux vector control (FVC) or sensorless vector

control (SVC).

Flux vector control uses the actual encoder value for speed feedback and, therefore,

requires an encoder mounted to the motor and connected to the drive.You program

the drive for FVC by first selecting UEC in parameter U.048, and then selecting the

PPR value of the encoder in parameter U.001.

Sensorless vector control (SVC) is an extension of the FVC regulator. It provides

performance close to FVC without using an encoder. Control is based on estimated

speed feedback. You program the drive for SVC by first selecting UEC in parameter

U.048 and then selecting SE in parameter U.001 (Encoder PPR).

Switching from one regulator type to the other (V/Hz to vector or vice versa) takes

approximately 5 seconds. The drive reinitiates power-up diagnostics (SELF appears

on the display and all LEDs turn on for approximately 4 seconds).

Changing this parameter also restores default values for all First and Second Menu

General parameters (P.---) as if a Restore Defaults command (P.050 = ON) was given.

However, this will NOT change the value of P.048 or P.049 (Country Defaults).

Important: All other parameter values must be verified if this parameter is changed

after initial programming, regardless of whether they are restored to their

default values.

P.048 Volts/Hertz or Vector Regulation

This parameter

selects the drive

regulator type:

volts/hertz (V/Hz) or

vector.

Parameter Range:

U-H = V/Hz control
UEC = vector control

Default Setting:

U-H

Parameter Type:

Configurable

Refer also to parameters:

U.001 Encoder PPR

P.049 Country Defaults

This parameter

selects the factory

default settings for

the First and Second

Menu General

parameters. USA

default settings are

listed throughout this

chapter. Refer to

Appendix E for the

European and

Japanese default

settings.

Parameter Range:

USA = USA default settings
EUr = European default settings
JPn = Japanese default settings

Default Setting:

USA

Parameter Type:

Configurable

Refer also to parameters:

N/A