Configuring the Digital Inputs When the RMI Board Is Installed in the Drive

F-1

A

PPENDIX

F

Configuring the Digital Inputs

When the RMI Board Is

Installed in the Drive

The GV3000/SE Regulator board contains three user-configurable digital inputs.

Parameters P.007 (Terminal Strip Digital Inputs Configure) and P.008 (Terminal Strip

Speed Reference Source) are used to specify how these digital inputs are used.

If an optional Remote Meter Interface (RMI) board is installed in the drive, four

additional digital inputs are available. RMI parameter r.030 is used to specify how the

RMI digital inputs are used.

The Regulator board digital inputs and the RMI digital inputs are not permitted to be

used for the same functions. One parameter cannot be set to a value which requires

resources (digital inputs) or a duplication of function which is used or defined by the

value of another parameter.

The acceptable values for P.008 are based on the value selected for P.007 and by the

value selected for r.030:

P.008 is limited by P.007 and r.030

P.007 is limited by P.008

r.030 is limited by P.008

First determine what functions are to be assigned to the three digital inputs on the

Regulator board. Once you have determined this, select the appropriate settings for

P.007 and P.008. As shown in the following tables,

the desired value for P.008 must

be permissible by both the P.007 and r.030 values. If either column indicates the

value is not acceptable, then P.008 cannot be set to that value. Use the following

tables to help determine the appropriate settings for your application.

Refer to chapter 4 in this manual for a complete description of parameters P.007 and

P.008 and their corresponding options. Refer to the RMI board instruction manual

(D2-3341) for a complete description of parameter r.030 and its options.