P.044 fault auto reset time – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 124

Advertising
background image

4-38

GV3000/SE AC Drive Software Reference, Version 6.06

P.043 Fault Auto Reset Attempts

(continued)

Table 4.5 lists the faults that can be auto reset:

All other faults cannot be auto reset.

Note that the auto reset feature will be disabled during the vector self-tuning operation
and the V/Hz identification procedure.

After the drive has detected the fault and is counting down the auto-reset time period,

the display will flash the countdown period in seconds in the following format:

"Ar30...Ar29...Ar28.........Ar01...Ar00"

If during this countdown, the operator presses the keypad STOP/RESET key, or

asserts the fault reset from the selected control source, the auto-reset countdown will

stop, and all faults will be reset.

Table 4.5 – Faults That Can Be Auto Reset

Fault Code

Description

AIn

4 to 20 mA analog input signal loss

bYC

DC bus charging bypass contactor

EC

Earth current failure (ground fault)

HIL

High line voltage

HU

High DC bus voltage

LU

Low DC bus voltage

nCL

Network communications loss

OC

Overcurrent steady state

OCA

Overcurrent while accelerating

OCb

Overcurrent during DC braking

OH

Drive overtemperature

OL

Electronic motor overload

UbS

Asymmetrical bus charge

P.044 Fault Auto Reset Time

This parameter

specifies the amount

of time the drive will

wait to attempt to

reset drive faults.

Parameter Range:

1 to 60 seconds

Default Setting:

8

Parameter Type:

Configurable

Refer also to parameters:

P.043 Fault Auto Reset Attempts

Advertising