P.029 elapsed time meter, P.030 elapsed time meter reset – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 119

Advertising
background image

Programming Reference

4-33

The presets are configured using parameters P.007 and P.008. P.008 must be set to

values of 2 through 7 for preset speeds. See table 4.4 and figure 4.6.

P.029 Elapsed Time Meter

This parameter

displays the number

of days (24-hour

periods) that the drive

has been under

power or the time

elapsed since the

Elapsed Time Meter

Reset (P.030)

parameter was last

reset.

Parameter Range:

0 to 9999 days

Default Setting:

N/A

Parameter Type:

Read only

Refer also to parameters:

P.030 Elapsed Time Meter Reset

P.030 Elapsed Time Meter Reset

This parameter sets

parameter P.029

(Elapsed Time Meter)

and the error log

clock to zero. This

parameter is set to

OFF after the reset

operation is carried

out.

Parameter Range:

OFF = No action
ON = Reset the Elapsed Time Meter (P.029) and the

error log clock to zero (0)

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.029 Elapsed Time Meter

P.031 to P.038 Preset Speed 1 through Preset Speed 8

These parameters

allow the setting of up

to eight different

preset speeds.

Parameter Range:

Minimum Speed (P.003) to Maximum Speed (P.004)

Default Setting:

5.0 Hz (V/Hz)

150 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters:

P.007 Terminal Strip Digital Inputs Configure

P.008 Terminal Strip Speed Reference Source