1-8
GV3000/SE AC Drive Software Reference, Version 6.06
Step 3.15 Press the ENTER key to display the default setting of P.004.
This shows that the default setting for
Maximum Speed is 60.0 Hz.
Step 3.16 Press the ▲
key to increase maximum speed or the ▼ key to decrease
maximum speed.
The adjustment range is:
15.0 Hz to the value set for H.022
(Overfrequency Limit).
The maximum value is 210 Hz.
VALUE ENTERED:
Step 3.17 Press the ENTER key to save the changed value.
After pressing ENTER, the same
parameter number is displayed. You can
now go to the next parameter.
!
ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of safe
operation at the maximum operating speed of the drive. In V/Hz
regulation, overfrequency protection in the drive is provided by means
of H.022. Failure to observe this precaution could result in bodily injury.