H.009 Avoidance Frequency Enable
(continued)
The adjusted values may be in any order. The frequency will not be affected at normal
acceleration or deceleration but will be avoided at continuous output frequency.
Figure 4.12 – Avoidance Frequency Band
Max Hz
AF 3
AF 2
AF 1
Avoidance
Frequency Band
Output
Frequency
Speed Reference
Min
Max
Min Hz
Base Frequency
H.010, H.012, H.014 Avoidance Frequency Midpoint 1, 2, and 3
This parameter
specifies the midpoint
of each avoidance
frequency band
selected in H.011,
H.013, and H.015.
Parameter Range:
0.0 to 200.0 Hz
Default Setting:
0.0
Parameter Type:
Tunable
Refer also to parameters:
H.009 Avoidance Frequency Enable
H.011, H.013, H.015 Avoidance Frequency Band 1,
2, and 3