P.064 option port: network trim reference source, P.065 option port: type and version – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 136

Advertising
background image

4-50

GV3000/SE AC Drive Software Reference, Version 6.06

The option port trim reference is used as the outer control loop reference and/or the

speed trim reference (see the P.014 (Trim Reference Source) parameter description).

In V/Hz regulation, the trim reference represents speed in hertz scaled 0 to 4095 for 0

to Maximum Speed (P.004).

In vector regulation, the trim reference represents speed scaled 0 to 4095 for 0 to Top

Speed (U.017). When used for the outer control loop, the value should be scaled

based on the scaling of the selected feedback.

Refer to the following option board manuals:

AutoMax Network Communication Option Board (D2-3308)

ControlNet Network Communication Option Board (D2-3390)

DeviceNet Network Communication Option Board (MAN0096-03)

PROFIBUS

Interface Board (49’1355)

Super Remote Meter Interface Board (D2-3341)

OCL Reference Selection (FVC/SVC Only)

The parameter is also used to select the OCL reference. Refer to Appendix H for more

information.

The display format is N.vvv, where N represents the option type (1 = RMI,

2 = AutoMax network or

PROFIBUS

network, 4 = DeviceNet network, and 5 =

ControlNet network) and vvv represents the software version number.
For example, if 2.103 is displayed, it means the drive is using the AutoMax network

option running software version 1.03.

P.064 Option Port: Network Trim Reference Source

This parameter

specifies where the

drive gets its trim

reference when the

option port is

selected as the

control source

(P.000 = OP)

.

Parameter Range:

Option board-dependent. See option board

instruction manual.

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

P.063 Option Port: Network Reference Source

U.000 Torque Reference Source

P.065 Option Port: Type and Version

This parameter

displays the option

type and the software

version number of the

option board.

Parameter Range:

N/A

Default Setting:

N/A

Parameter Type:

Read only

Refer also to parameters:

N/A