Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual
Page 23

Starting Up the Drive for Volts/Hertz Regulation
1-9
Step 3.18 Press the ▲
key to display P.005, Current Limit.
This parameter sets Current Limit,
which corresponds to the value in
parameter P.095, Power Module Output
Amps.
Step 3.19 Press the ENTER key to display the default setting of P.005.
This shows that the default setting for
Current Limit is 100.
Step 3.20 Press the ▼
key to decrease current limit. Decrease current limit only if
the motor nominal current rating is less than the drive nominal current
rating.
Use the following equation to calculate
current limit:
(1)
From motor nameplate
(2)
See the hardware reference manual
for ratings
Adjustment Range: 50 to 110
VALUE ENTERED: