Programming Reference

4-81

.

If this feature is enabled and DC bus voltage drops below 80% of nominal, the drive

decelerates the motor enough to maintain bus voltage. Alarm code LIL appears on the

display while the drive is regulating the DC bus. Note that the lighter the load, the

longer the power dip ride-through time can be. When input power is restored, the drive

ramps to the reference speed.

If this feature is enabled, and the DC bus voltage drops while the drive is stopped, LIL

will be displayed.

This parameter is not related to P.042 (Line Dip Ride-Through Time).

U.022 Motor Nameplate Horsepower

This parameter

identifies the motor

horsepower as it

appears on the motor

nameplate.

Parameter Range:

0.3 to 600.0 HP

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters:

U.002 Motor Poles

U.003 Motor Nameplate Base Frequency

U.004 Motor Nameplate Amps

U.005 Motor Nameplate RPM

U.006 Magnetizing Current

U.007 Motor Nameplate Volts

U.023 Low DC Bus Fault Avoidance Enable

This parameter

selects how the drive

responds to power

loss (line dip

condition).

This feature applies

to SVC applications

only and is not

available if the drive

is configured as a

torque regulator.

Parameter Range:

OFF = Drive will not regulate the DC bus on a line

dip condition

ON = Drive will decelerate the motor to attempt to

hold up the DC bus on a line dip condition

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

N/A