Programming Reference

4-47

Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055. .

Note that if P.000 = rE, but the REMOTE/LOCAL switch at terminal 17 is set for

LOCAL (closed), the STOP key is active even if P.055 is set to ON.

P.055 STOP/RESET Key Disable

This parameter

disables the

STOP/RESET key

except from the

selected control

source.

Parameter Range:

OFF = Enable the STOP/RESET key regardless of

the control source

ON = Disable the STOP/RESET key except from the

selected control source

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.000 Control Source

!

ATTENTION: When P.055 is set to ON, the STOP/RESET key is

functional only from the selected control source. As a safety precaution,

Reliance Electric recommends that an emergency stop push button be

located near the drive in an easily accessible location. As a further safety

precaution, the user should post a warning on the drive to alert personnel

that the STOP/RESET key is not functional. Failure to observe this

precaution could result in severe bodily injury or loss of life.

Table 4.7 – STOP/RESET Key Status Based on P.000 and P.055

Control Source

(P.000 =)

P.055

Front Panel

STOP/RESET Key

OIM/CS3000

STOP/RESET Key

Front panel (LOCL)

OFF

Active

Active

Terminal strip (rE)

OFF

Active

Active

Network/option port (OP)

OFF

Active

Active

OIM/CS3000 (SErL)

OFF

Active

Active

Front panel (LOCL)

ON

Active

Inactive

Terminal strip (rE)

ON

Inactive

Inactive

Network/option (OP)

ON

Inactive

Inactive

OIM/CS3000 (SErL)

ON

Inactive

Active