5.7 Overview of NuDAM-6060

NuDAM-6060 provides four relay output channels, two are form A and two
are form C. It can control high power devices without external circuits. The
isolation guarantees the industrial safety.

5.7.1 Features of NuDAM-6060

z

4 channels relay output

z

4 channels isolated digital input

z

Programmable host watchdog timer for host failure protection

z

Internal watchdog timer for device failure protection

z

Easy programming by software

z

Easy installation and wiring

5.7.2 Specifications of NuDAM-6060

‹ Interface

Interface : RS-485, 2 wires

Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K,

115.2K (115.2K only for firmware reversion above
A4.00)

‹ Input

Channel numbers : 4

Common External Voltage : +24 V

‹ Output

Channel numbers : 4 relay output

Output type : 2 form C channels, 2 form A channels

Contact rating : 0.5A / AC 125V,1A / DC 30V

Relay ON/OFF time interval :Max. 3 ms

Breakdown voltage : 750 V

rms

(between open contact),1000

V

rms

(between contact and coil)

Expected life : 10

5

times(0.5A/AC125V resistive load at 20 cpm) or

10

8

times(no load at 180 cpm)

Insulation resistance :Min. 1000 M

Ω

‹ Watchdog Function