6.7.30 Read Alarm Limit Value of Counter 1

@Description

Read the alarm limit value of counter 1.

@Syntax

@(Addr)RA<CR>

@

Command leading code.

(Addr)

Address ID (2-character)

RA

Read alarm limit value command code

@Response

!(Addr)(ArmData)<CR>
or
?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(ArmData)

The alarm limit value which consists of 8 hexadecimal
digits.

@Example

User command:

@30RA<CR>

Response:

!300001FFFF<CR>

Item Meaning

Description

@

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

RA

Read alarm limit value of counter 0.

!

Command is valid.

30

Address of counter/frequency module.

0001FFFF 131071(0x0001FFFF).