157
6.3.8 Read CJC Status
@Description
Read the CJC (Cold Junction Compensation) sensors data.
@Syntax
$(Addr)3<CR>
$
Command leading code.
(Addr) Address
ID
3
Read CJC status.
@Response
>(Data)<CR>
or
?(Addr)<CR>
>
Command is invalid.
(Data)
CJC sensor’s data.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point. The
resolution is 0.1
°C
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
$063<CR>
Response:
>+0037.9<CR>
This command is to read analog input module CJC status at
address 06H, return data is 37.9
°C.