6.7.19 Set Minimum Input Signal Width at Low Level

@Description

Set the minimum input signal width at low level, for signal level low
less then this value will be filtered out as noise.

@Syntax

$(Addr)0L(MinFData)<CR>

$

Command leading code.

(Addr)

Address ID (2-character)

0L

Set minimum input signal width at low level command
code.

(MinFData)

The minimum width data at low level. The unit is

μs

and its resolution is 1

μs. This value range from 4 μs

to 1020

μs, which is a 4-digit integer. (4-character)

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

$300L0010<CR>

Response:

!30<CR>

Item Meaning

Description

$

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

0L

Set minimum input signal width.

0010 (MinFData)

10

μs