8.3 Hexadecimal or Two’s Complement Hexadecimal

Hexdecimal Format

Hexdecimal Format is for ND-602x modules.The data is in
hexdecimal format as the bit 1 and 0 are set as ‘10’. The data
string length is 3 characters. It is equivilant to 12 binary bits.
Because the output of ND-6021 is unipolar, the maximum value
of the digits is FFF(H) and the minimum value of the digits is
000(H).
As the output range is set to 0~20mA, the value ‘FFF(H)’
represents 20mA and ‘000(H)’ represents 0mA. Similarily, as
the output range is set to 4~20mA, the value ‘FFF(H)’ represents
20mA and ‘000(H)’ represents 4mA.
The different analog output ranges have different resolutions.
Refer to Table 8-8 for details.

Code

Output

Range

Data

Format

Maximum

Value

Minimum

Value

Output

Resolution

30

0 to 20 mA

Hexdecimal

FFF 000 4.88

μA

31

4 to 20 mA

Hexdecimal

FFF 000 4.88

μA

32

0 to 10 V

Hexdecimal

FFF 000

2.442

mV

Table 8-8 Analog Output Range and resolution<ND-6021,ND-6024>

‹ Example 1 :

If the output range is set as 0 to 20 mA

The desired analog output current is 10 mA

Hexdecimal Format: 7FF<CR>

Two’s Complement Hexadecimal

Two’s Complement Hexadecimal is for ND-601x modules.
• Data format bit 1 and 0 set to 10 is 2’s complement
• Data is 4-character(16 binary bits) hexadecimal string
• Positive full scale is 7FFF (+32767)
• Negative full scale is 8000 (-32768)

The different analog input ranges have different resolutions.
Refer to Table 8-9 and Table 8-10 for details.