6.7.28 Set Alarm Limit Value of Counter 1

@Description

Set the alarm limit value of counter 1.

@Syntax

@(Addr)SA(ArmData)<CR>

@

Command leading code.

(Addr)

Address ID (2-character)

SA

Set alarm limit value command code.

(ArmData)

The alarm limit value which consists of 8 hexadecimal
digits.

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

@30SA0002FFFF<CR>

Response:

!30<CR>

Item Meaning Description
@

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

SA

Set alarm limit value of counter
1.

0002FFFF (ArmData)

196607(0x0002FFFF)

(6080)