6.7.28 Set Alarm Limit Value of Counter 1
@Description
Set the alarm limit value of counter 1.
@Syntax
@(Addr)SA(ArmData)<CR>
@
Command leading code.
(Addr)
Address ID (2-character)
SA
Set alarm limit value command code.
(ArmData)
The alarm limit value which consists of 8 hexadecimal
digits.
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
@30SA0002FFFF<CR>
Response:
!30<CR>
Item Meaning Description
@
(Leading Code)
Command leading code.
30
(Addr)
Address ID is 30H.
SA
Set alarm limit value of counter
1.
0002FFFF (ArmData)
196607(0x0002FFFF)