6.4.7 Trim Calibration

@Description

Trims the specified analog output module a specified number
of units up or down.

@Syntax

$(Addr)3(Counts)<CR>

$

Command leading code

(Addr) Address

ID

3

Function Code

(Counts)

Number of counts to increase or decrease the output
current.
Range 00 - 5F : 0 to +95 counts (increase)
Range A1 - FF : -95 to -1 counts (decrease)
1 count equals approximately 4.88

μA or 2.44mV

(4.88mV for ND-6024)

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

$06314<CR>

Response:

!06<CR>

Increase analog output value about 97.6

μA (14H * 4.88μA = 97.6μA) at

address 06H.

Note : Analog output module trim calibration should have a

corrent calibration wiring. Refers to Chapter 9 “Analog
Output Calibration” for details.