2 summary of command set – ADLINK ND-6067 User Manual

Page 130

Advertising
background image

128

6.2 Summary of Command Set

There are three categories of NuDAM commands. One is the general
commands, including set configuration command, read configuration, reset,
read module‘s name or firmware version, etc. Every NuDAM can response
to the general commands.

The second category is the functional commands, which depends on
functions of each module, not every module can execute all functions.

The third category is the special commands, including functions about the
programmable watchdog timer, safe values, and the programmable leading
code.

Command Set of Digital I/O Modules

Command Syntax

Module

Section

General Commands

Set Configuration

%(OldAddr)(NewAddr)

(TypeCode)(BaudRate)(C

heckSumFlag)

601x,602x,

605x,606x

6080,6531

6.2.1

Read Configuration

$(Addr)2

601x,602x,

605x,606x

6080,6531

6.2.2

Read Module Name

$(Addr)M

601x,602x,

605x,606x

6080,6531

6.2.3

Read Firmware Version

$(Addr)F

601x,602x,

605x,606x

6080,6531

6.2.4

Reset Status

$(Addr)5

601x,602x,

605x,606x

6080,6531

6.2.5

Soft Reset

$(Addr)RS

601x,602x,

605x,606x

6080,6531

6.2.6

Analog I/O Modules Functional Commands

Read Analog Data Channel 0

#(Addr)

6013

6.3.1

Offset Calibration to each Channel

#(Addr)1(Channel No)

6013

(11)

6.3.2

Span Calibration to ach Channel

$(Addr)0(Channel No)

6.3.3

Read Analog Data From

Channel N

#(Addr)(ChannelNo)

6013,6017,

6018

6.3.4

Read All Analog Data Channel

$(Addr)A

6013,6017,

6018

6.3.5

Advertising