144
(DataFlag)
Current setting of module setting and
RS-232 configuration refer to Table 6-4
for details. (4-character, WXYZ)
6531
@Example 1 <ND-601x>
User command:
$302<CR>
Response:
!30050600<CR>
!
Command is valid.
30 Address
ID.
05
Analog input range is
±2.5 V.
06
Baud rate is 9600 bps.
00
checksum is disable.
@Example 2 <ND-602x>
User command:
$182<CR>
Response:
!18320610<CR>
!
Command is valid.
18 Address
ID.
32
Analog output range is 0 to 10V
06
Baud rate is 9600 bps.
10
The output data is in engineering units, slew rate is 1mA/sec,
checksum is disable.
@Example 3 <ND-605x>
User command:
$302<CR>
Response:
!30400600<CR>
!
Command is valid.
30 Address
ID.
40
Digital I/O module.
06
Baud rate is 9600 bps.
00
checksum is disable.