ADLINK ND-6067 User Manual

Page 86

Advertising
background image

84

5.3 Overview of ND-6053

ND-6053 provides 16 digital input channels for dry contact or wet contact
signals. The effective distance from DI to contact point is up to 500 meter for
dry contact input.

5.3.1 Features of ND-6053

z

16 bits digital input

z

Programmable host watchdog timer for host failure protection

z

Internal watchdog timer for device failure protection

z

Easy programming by software

z

Easy installation and wiring

5.3.2 Specifications of ND-6053

‹ Interface

Interface : RS-485, 2 wires

Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K,

115.2K

‹ Input

Channel numbers : 16

Dry Contact:

Logical level 0 : close to GND

Logical level 1 : open

Wet Contact :

Switching Level :TTL

Maximum current sink : 50mA

‹ Watchdog Function

Module internal watchdog timer : 150ms

Power failure threshold : 4.65 V

Host programmable watchdog : 100 ms ~ 25.5 sec

‹ Power

Power supply : +10V to +30V

Current consumption : 0.408 W

Advertising