ADLINK ND-6067 User Manual

Page 264

Advertising
background image

262

Code

Input

Range

Data

Format

+Full

Scale

Zero

- Full

Scale

Displayed

Resolutio

n

00

±15mV

2’s Comp.

7FFF

0000

8000

1 LSB

01

±50mV

2’s Comp.

7FFF

0000

8000

1 LSB

02

±100mV

2’s Comp.

7FFF

0000

8000

1 LSB

03

±500mV

2’s Comp.

7FFF

0000

8000

1 LSB

04

±1V

2’s Comp.

7FFF

0000

8000

1 LSB

05

±2.5V

2’s Comp.

7FFF

0000

8000

1 LSB

06

±20mA

2’s Comp.

7FFF

0000

8000

1 LSB

07

Reserved

08

±10V

2’s Comp.

7FFF

0000

8000

1 LSB

09

±5V

2’s Comp.

7FFF

0000

8000

1 LSB

0A

±1V

2’s Comp.

7FFF

0000

8000

1 LSB

0B

±500mV

2’s Comp.

7FFF

0000

8000

1 LSB

0C

±150mV

2’s Comp.

7FFF

0000

8000

1 LSB

0D

±20mA

2’s Comp.

7FFF

0000

8000

1 LSB

Table 8-9 Analog Input Range and resolution<ND-6017,ND-6018>

Code

Input Range

Thermocouple

Data

Format

Maximum

Minimum

Displayed

Resolution

0E

J (0

°C to 760°C)

2’s Comp.

7FFF

0000

1 LSB

0F

K (0

°C to 1000°C)

2’s Comp.

7FFF

0000

1 LSB

10

T (-100

°Cto400°C)

2’s Comp.

7FFF

E000

1 LSB

11

E (0

°C to 1000°C)

2’s Comp.

7FFF

0000

1 LSB

12

R (500

°C to 1750°C)

2’s Comp.

7FFF

2492

1 LSB

13

S (500

°C to 1750°C)

2’s Comp.

7FFF

2492

1 LSB

14

B (500

°C to 1800°C)

2’s Comp.

7FFF

238E

1 LSB

15

N (-270

°C to 1300°C)

2’s Comp.

7FFF

E56B

1 LSB

16

C (0

°C to 2320°C)

2’s Comp.

7FFF

0000

1 LSB

Table 8-10 Thermocouple Type ,Temperature Range and resolution <ND-6018>

‹ Example 2:

Input Range is

±5 V

Input is +1 Volts

Two’s complement hexadecimal: 1999<CR>
((1/5) x 32768) = 6553.6 = 1999H

‹ Example 3:

Input Range is

±5 V

Input is -2 Volts

Advertising