ADLINK ND-6067 User Manual

Page 139

Advertising
background image

137

@Example 2 <ND-602x>

User command:

%0118310610<CR>

Response:

!18<CR>

Item Meaning

Description

%

(Leading Code)

Command leading code.

01

(OldAddr)

Original address ID is 01(Hex).

18

(NewAddr)

New address ID is 18(Hex).

31 (OutputRange)

Analog

output range is 4 to 20 mA

06

(BaudRate)

Baud rate is 9600.

10

(DataFormat)

10 means a slew rate is 1.000 mA/sec
and checksum is disable.

<CR> Carriage

return 0x0D.

Code
(Hex)

Signal Range of Output Range

Modules

30

0 to 20 mA

6021

31

4 to 20 mA

6021

32

0 to 10 V

6021

33

-10 to 10 V

6024

Table 6-2 Analog Output Range Setting

@Example 3 <ND-605x>

User command:

%0130400600<CR>

Response:

!30<CR>

Item Meaning

Description

%

(Leading Code)

Command leading code.

01

(OldAddr)

Original address ID is 01H.

30

(NewAddr)

New address ID is 30H (Hex).

40

(TypeCode)

Digital I/O module.

06

(BaudRate)

Baud rate is 9600.

00

(CheckSumFlag)

00 means checksum is disable.

<CR> Carriage

return

0x0D.