6.7.16 Read Filter Status

@Description

Read the digital filter enable/disable status.

@Syntax

$(Addr)4<CR>

$

Command leading code.

(Addr)

Address ID (2-character)

4 Enable/Disable

filter command code.

@Response

!(Addr)(FStatus)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(FStatus)

0: disable filter
1: enable filter

@Example

User command:

$304<CR>

Response:

!301<CR>

Item Meaning

Description

$

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

4

Enable/Disable

filter command.

!

Command is valid.

30

Address of counter/frequency module.

1

Digital filter is enable.