119

5.10.1 Features of NuDAM-6080

z

Two 32 bit counter / frequency input channel

z

Two digital output channels of open collector type

z

5000 Vrms isolation voltage for isolated input mode

z

External gate control for counter input

z

Alarm function with alarm output

z

Programmable digital filter for noise rejection

z

Programmable threshold setting of trigger level for non-isolated input
mode

z

Programmable host watchdog timer for host failure protection

z

Internal watchdog timer for device failure protection

z

Easy programming by software

z

Easy installation and wiring

5.10.2 Specifications of NuDAM-6080

‹ Interface

Interface : RS-485, 2 wires

Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K

‹ Counter Input

Two independent 32 bit counters

Input frequency: 20 kHz max.

Input mode: Isolated or non-isolated

Isolated input level:

Logic level 0: +1V max.
Logic level 1: +3.5V to +30V

Isolation voltage: 5000 Vrms

Non-isolated input level (programmable threshold):

Logic level 0: 0 to +5V (default = 0.8V)
Logic level 1: 0 to +5V (default = 2.4V)

Input pulse width > 5

μsec.

Programmable digital noise filter: