6.4.6 20mA Calibration
@Description
Stores the current output value as 20 mA reference at the
specified analog output module. (only 6021)
@Syntax
$(Addr)1<CR>
$
Command leading code (1 character)
(Addr)
Address ID (2 characters)
1
Function Code, 20 mA calibration (1 character)
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
$061<CR>
Response:
!06<CR>
To perform the 20 mA calibration for analog input module at address ID
06H.
Note : Analog output module should be trimmed to the correct
value by “Trim Calibration” command before to execute
“20 mA Calibration”. Refers to Chapter 9 “Analog Output
Calibration” for details .
(6021)