6.4.6 20mA Calibration

@Description

Stores the current output value as 20 mA reference at the
specified analog output module. (only 6021)

@Syntax

$(Addr)1<CR>

$

Command leading code (1 character)

(Addr)

Address ID (2 characters)

1

Function Code, 20 mA calibration (1 character)

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

$061<CR>

Response:

!06<CR>

To perform the 20 mA calibration for analog input module at address ID
06H.

Note : Analog output module should be trimmed to the correct

value by “Trim Calibration” command before to execute
“20 mA Calibration”. Refers to Chapter 9 “Analog Output
Calibration” for details .

(6021)