126

Example 2: checksum is enable

User Command: $012B7<CR>

Response: !01400600AC<CR>

$ :

LeadingCode

01 :

Address

2

: Command (Read Configuration)

B7

: Checksum value

<CR>

: Carriage return 0x0D

‘$’ = 0x24

‘0’ = 0x30

‘1’ = 0x31

‘2’ = 0x30

B7 = ( 0x24 + 0x30 + 0x31 + 0x32 ) MOD 0x100

‘!’ = 0x21

‘0’ = 0x30

‘1’ = 0x31

‘4’ = 0x34

‘6’ = 0x36

AC = ( 0x21 + 0x30 + 0x31 + 0x34 + 0x30 + 0x30 + 0x36 + 0x30

+ 0x30 ) MOD 0x100

Note: 1.There is no spacing between characters.

2. At end of command need a <CR> carriage return 0x0D.
3. Checksum is optional parameter.