6.7.27 Set Alarm Limit Value of Counter 0
@Description
Set the alarm limit value of counter 0.
@Syntax
@(Addr)PA(ArmData)<CR>
@
Command leading code.
(Addr)
Address ID (2-character)
PA
Set alarm limit value command code.
(ArmData)
The alarm limit value which consists of 8 hexadecimal
digits.
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
@30PA00020000<CR>
Response:
!30<CR>
Item Meaning
Description
@
(Leading Code)
Command leading code.
30
(Addr)
Address ID is 30H.
PA
Set alarm limit value of counter 0.
00020000 (ArmData)
131072(0x00020000)