ADLINK ND-6067 User Manual

Page 224

Advertising
background image

222

6.7.27 Set Alarm Limit Value of Counter 0

@Description

Set the alarm limit value of counter 0.

@Syntax

@(Addr)PA(ArmData)<CR>

@

Command leading code.

(Addr)

Address ID (2-character)

PA

Set alarm limit value command code.

(ArmData)

The alarm limit value which consists of 8 hexadecimal
digits.

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

@30PA00020000<CR>

Response:

!30<CR>

Item Meaning

Description

@

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

PA

Set alarm limit value of counter 0.

00020000 (ArmData)

131072(0x00020000)

(6080)

Advertising
This manual is related to the following products: