6.5.4 Digital Input

@Description

Read the digital input channel value and readback the digital
output channel value.

@Syntax

$(Addr)6<CR>

$

Command leading code.

(Addr) Address

ID

6

Digital data input command.

@Response

ND-6050 module response :

!(DataOut)(DataIn)00<CR>

ND-6052 module response :

!(DataIn)0000<CR>

ND-6053 module response :

!(DataInH)(DataInL)00<CR>

ND-6054 module response :

!(DataInH)(DataInL)00<CR>

ND-6056 module response :

!(DataOutH)(DataOutL)00<CR>

ND-6058 module response :

!(IoFlag)(DataIn)(DataA)(DataB)(DataC)<CR>

ND-6060 module response :

!(DataOut)(DataIn)00<CR>

ND-6063 module response :

!(DataOutH)0000<CR>
or
?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(DataOut)

Value of digital output channel. (2-character)

(DataIn)

Value of digital input. (2-character)

(DataInH)

Value of digital input channel 15-8.
(2-character)

(DataInL)

Value of digital input channel 7-0.(2-character)

(DataOutH)

Value of digital output channel 15-8.
(2-character)

(DataOutL)

Value of digital output channel 7-0.(2-character)

(DataA)

Value of digital channel 7-0.(2-character)

(DataB)

Value of digital channel 7-0.(2-character)

(DataB)

Value of digital channel 7-0.(2-character)

(6050,6052, 6053,6054,

6058,6060)

Advertising