ADLINK ND-6067 User Manual

Page 219

Advertising
background image

217

6.7.22 Read TTL Input High Trigger Level

@Description

Read the TTL input high trigger level.

@Syntax

$(Addr)1H<CR>

$

Command leading code.

(Addr)

Address ID (2-character)

1H

TTL input high trigger level command code.

@Response

!(Addr)(ThData)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(ThData)

The high trigger level for TTL input. The unit is 0.1 V
and its resolution is 0.1 V too. This value range from
0.1 to 5V, which is a 2-digit integer.

@Example

User command:

$301H<CR>

Response:

!3024<CR>

Item Meaning

Description

$

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

1H

Read TTL input high trigger level.

!

Command is valid.

30

Address of counter/frequency module.

24

The high trigger level is 2.4 V.

(6080)

Advertising
This manual is related to the following products: