ADLINK ND-6067 User Manual

Page 223

Advertising
background image

221

6.7.26 Disable Alarm

@Description

Disables alarm function of counter 0 or counter 1.

@Syntax

@(Addr)DA(CounterNo)<CR>

@

Command leading code.

(Addr)

Address ID (2-character)

DA

Enable alarm command code.

(CounterNo)

0: counter 0
1: counter 1

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

@30DA0<CR>

Response:

!30<CR>

Item Meaning

Description

@

(Leading Code)

Command leading code.

30

(Addr)

Address ID is 30H.

DA

Disable alarm command code.

0 (CounterNo) Counter

0.

(6080)

Advertising
This manual is related to the following products: