ADLINK ND-6067 User Manual

Page 51

Advertising
background image

49

2.4.6 Initialation & Installation

Software Installation

1. If you have already installed “NuDAM Administration” then skip other steps.

2. Backup your software diskette

3. Insert “NuDAM Administration” disc into CD-ROM:

4. Change drive to the path of CD-ROM. For example, your drive of CD-ROM is

F:, then change the drive to F:

5. Find the setup of NuDAM Administration and run it.

6. Please follow the steps of setup program then you can successful to install the

nudism Administration.

Objective of Initializing a Brand-New ND-6531

All NuDAM modules. except ND-6520, ND-6510, and ND-6530, in a RS-485
network must have an unique address ID, however, every brand-new ND-6531
has a factory default setting as following:

Address ID is 01.

Baud rate is 9600 bps

RS-485 Interface

Host Watchdog timer is disable

Therefore, to configure the brand-new NuDAM before using is necessary,
otherwise the address ID will conflict with other modules if the ID of new module
is identical to any of the existing one. The baud rate may also be changed
according to user‘s requirement.

Default State

The NuDAM I/O modules must be set at Default State when you want to change
the default settings, such as the ID address, baud rate, check-sum status etc.
All NuDAM I/O modules have a special pin labeled as DEFAULT*. The module
will be in Default State if the DEFAULT* pin is shorted to ground when power
ON. Under this state, the default configuration is set as following:

Address ID is 00.

Baud rate is 9600 bps.

RS-485 Interface

8 Data bits,1 Start bit,1 Stop bit and none parity check.

Advertising
This manual is related to the following products: